Omron Inductive Proximity switch E2B-M12LS04-WP-B1 WP-C1 E2B-M12LS04-WZ-C1 WZ-C2
789.00฿
Omron inductive proximity switch E2B-M12LS04-WP-B1 WP-C1 E2B-M12LS04-WZ-C1 WZ-C2
General Description – E2B Series
The Omron E2B series is a general-purpose inductive proximity sensor line designed for reliable detection of metal objects in industrial automation environments.
These sensors operate by generating a high-frequency electromagnetic field at the sensing face. When a metal object enters the sensing range, the electromagnetic field is disturbed, causing the output to switch state.
They are widely used for:
Metal part detection
Position sensing
End-of-travel detection
Counting metal components
Machine automation feedback
Common Technical Specifications (E2B-M12LS04 Base Model)
Parameter | Specification |
|---|---|
Sensor Type | Inductive proximity switch |
Target Material | Metal only |
Sensing Distance | 4 mm (nominal) |
Housing Size | M12 threaded cylindrical |
Mounting Type | Flush (shielded) |
Supply Voltage | 12–24 VDC |
Protection Rating | IP67 |
Indicator | Built-in LED status indicator |
The “M12” indicates a 12 mm diameter threaded body.
The “LS04” indicates approximately 4 mm sensing distance.
Because this is a flush (shielded) type, it can be mounted flush with metal surfaces without affecting detection stability.
Model Differences and Output Types
The difference between WP and WZ versions primarily relates to output polarity and wiring configuration.
A) E2B-M12LS04-WP-B1
Output type: NPN
Switching mode: Normally Open (NO)
Wiring: Pre-wired cable
Typical application: PLC systems configured for sinking inputs
B) E2B-M12LS04-WP-C1
Output type: NPN
Wiring configuration variant (connector or cable specification differs from B1)
Same sensing distance: 4 mm
Same mechanical size: M12
C) E2B-M12LS04-WZ-C1
Output type: PNP
Switching mode: Normally Open (NO)
Wiring: Typically connector type
Used for PLC systems requiring sourcing inputs
D) E2B-M12LS04-WZ-C2
Output type: PNP
Connector or wiring configuration variant
Same sensing and mechanical characteristics
NPN vs PNP Output Explanation
NPN Output:
When the sensor detects metal, the output switches to 0 V (ground).
Used with PLC inputs configured as sinking type.
PNP Output:
When the sensor detects metal, the output switches to +24 V.
Used with PLC inputs configured as sourcing type.
It is critical to match the sensor output type with the PLC input configuration.
Electrical Wiring (Typical 3-Wire DC Sensor)
Standard wire colors:
Brown → +24 VDC
Blue → 0 V (GND)
Black → Output signal
Incorrect polarity connection may damage the sensor.
Installation Considerations
Maintain proper mounting torque on the M12 threaded body.
Ensure no unintended metal objects are within sensing range.
Confirm the target size is sufficient to achieve full sensing distance.
For flush types, follow recommended installation spacing from adjacent sensors.
Typical Industrial Applications
These sensors are suitable for:
Conveyor metal detection
Metal bracket presence verification
Machine tooling position feedback
Robotic fixture detection
End-stop detection in automation equipment
Summary Comparison
Model | Output Type | Sensing Distance | Housing | Typical Use |
|---|---|---|---|---|
WP-B1 | NPN | 4 mm | M12 | Sinking PLC input |
WP-C1 | NPN | 4 mm | M12 | Sinking PLC input |
WZ-C1 | PNP | 4 mm | M12 | Sourcing PLC input |
WZ-C2 | PNP | 4 mm | M12 | Sourcing PLC input |
All models are electrically similar except for output polarity and connection style.
Obione